Open Access Open Access  Restricted Access Subscription Access

Image Charge effect on Metallic Particle Movement in a single phase Gas Insulated Bus Duct with Dielectric Coated Enclosure

Challa Krishna Rao, Kalyana Kiran

Abstract


This paper presents the movement of a wire particle inside a single phase GIB(Gas Insulated Bus duct) .The movement of a particle is not only influenced by the electric fields produced by the conductor but also effected by the fields due to its Image charge .In view of this ,the present work analyzes the effect of Image charge also on the movement of the particle .The equations governing the motion of the particle due to Image charge has been developed, for the first time, to obtain the particle trajectories. Further, the enclosure in a GIB may be coated with a dielectric material to restore some of the dielectric strength of the compressed gas that is lost due to surface roughness and contamination with conducting particles. Hence, simulation has been carried out to study the effect of fields on the motion of the particle with and without Image charge effect and also with and without dielectric coating on the enclosure. Trajectories obtained for various voltages of aluminum and copper particles are presented and duly discussed.

 

Keywords: Metallic particles, electrostatic effect, image charge effect, gas insulated substations, gas insulated transmission line, gas insulated bus duct


Full Text:

PDF

References


Prakash, K. S., Srivastava, K. D., & Morcos, M. M. (1997). Movement of particles in compressed SF/sub 6/GIS with dielectric coated enclosure. IEEE transactions on dielectrics and electrical insulation, 4(3), 344-347.

Anis, H., & Srivastava, K. D. (1981). Free conducting particles in compressed gas insulation. IEEE Transactions on electrical insulation, (4), 327-338.

Laghari, J. R., & Qureshi, A. H. (1981). A review of particle-contaminated gas breakdown. IEEE Transactions on Electrical Insulation, (5), 388-398.

Srivastava, K. D., & Van Heeswijk, R. G. (1985). Dielectric coatings-effect on breakdown and particle movement in GITL systems. IEEE transactions on Power Apparatus and Systems, (1), 22-31.

Morcos, M. M., Zhang, S., Srivastava, K. D., & Gubanski, S. M. (2000). Dynamics of metallic particle contaminants in GIS with dielectric-coated electrodes. IEEE Transactions on Power Delivery, 15(2), 455-460.

Anis, H., & Srivastava, K. D. (1981). Free conducting particles in compressed gas insulation. IEEE Transactions on electrical insulation, (4), 327-338.

Moreos, M. M., Srivastava, K. D., & Anis, H. (1983). Dynamics of metallic contaminants in compressed gases. In IEEE Int. Conf. on Industrial Applications.

Amarnath, J., Singh, B. P., Kamaksaiah, S., & Radhakrishna, C. (1999, October). Determination of particle trajectory in gas insulated bus duct by Monte-Carlo technique. In 1999 Annual Report Conference on Electrical Insulation and Dielectric Phenomena (Cat. No. 99CH36319) (pp. 399-402). IEEE.

Amarnath, J., Kamakshaiah, S., Singh, B. P., & Srivastava, K. D. (2001, April). Influence of Power Frequency and Switching Impulse Voltage on Particle Movement in GIS–Predicted by Monte-Carlo Technique. In IEEE, Intern. High Voltage Workshop, California, USA.


Refbacks