Open Access Open Access  Restricted Access Subscription Access

Very Fast Transient Overvoltage Analysis on 245 kV Gas Insulated Substation

Anuj Paul, Kartik Kapse, Nilesh Chaudhari, Pavan Karpe, R. A. Ahire

Abstract


Gas-insulated Substations play an important role in power systems today but are adversely affected by the generation of Very Fast Transient Overvoltages (VFTO). This paper presents an analysis of VFTOs generated in a 245kV GIS caused by the operation of the circuit breaker and disconnector. The entire substation is modelled in PSCAD-EMTDC using equivalent circuits to simulate the operation of the disconnector and circuit breaker. The VFTO is observed for its peak voltage, rise time and voltage gradient. The results from the simulation were discussed and it was found that the VFTO does not damage the system insulation.

 

Keywords: Disconnector, GIS, PSCAD, VFTO


Full Text:

PDF

References


Kapur, A. K., & Malik, A. K. (1991, August). Gas insulated substations in India-an overview. In TENCON'91. Region 10 International Conference on EC3-Energy, Computer, Communication and Control Systems (Vol. 1, pp. 461-466). IEEE.

Koch, H. J. (Ed.). (2014). Gas insulated substations. John Wiley & Sons.

Insulation Co-ordination - Part 1: Definitions, principles and rules IS/IEC 60071-1: 2006.

CIGRE, W. (1990). 33.02, Guidelines for representation of network elements when calculating transients. CIGRE Technical Brochure, 39.

Povh, D., Schmitt, H., Valcker, O., & Wutzmann, R. (1996). Modelling and analysis guidelines for very fast transients. IEEE Transactions on Power Delivery, 11(4), 2028-2035.

Lu, T., & Zhang, B. (2005, August). Calculation of very fast transient overvoltages in GIS. In 2005 IEEE/PES Transmission & Distribution Conference & Exposition: Asia and Pacific (pp. 1-5). IEEE.

Liu, S., Sheng, C., Meng, F., Wang, S., Wang, R., Zhang, Y., ... & He, W. (2016, September). Electric field disturbance caused by an unmanned aerial vehicle flying near the HV power transmission line. In 2016 IEEE International Conference on High Voltage Engineering and Application (ICHVE) (pp. 1-4). IEEE.

Kumar, A., & Mishra, M. K. (2008, December). VFT study for EHV-GIS substation. In National Power Systems Conference (NPSC).

Pinches, D. S., & Al-Tai, M. A. (2008, September). Very fast transient overvoltages generated by gas insulated substations. In 2008 43rd International Universities Power Engineering Conference (pp. 1-5). IEEE.

Rao, J. R., Amarnath, J., & Kamakshaiah, S. (2010, October). Accurate modelling of very fast transient overvoltages in a 245kV GIS and research on protection measures. In 2010 Annual Report Conference on Electrical Insulation and Dielectic Phenomena (pp. 1-4). IEEE.


Refbacks

  • There are currently no refbacks.